Parcel: Unknown

Address:
2513 E 6TH ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM07345
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/29/2020 JPEELDA1 FIRE REVIEW Approved
11/10/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Clarify the size of the horizontal drain exiting the new restrooms. It is labeled 3" on B/P3 but 4" on 1/P2 and 1/P1. Reference: Section 107.2.1, IPC 2018.
2. Provide urinal partitions in the new men's restroom. Reference: Section 405.3.5, IPC 2018.
3. Floor sinks in the kitchen shall discharge through a grease interceptor. Reference: Section 1003.3, IPC 2018, as amended by the City of Tucson.
4. Hand sinks (SK-1) in the kitchen are allowed to connect to the sanitary waste system instead of the grease waste system only if each sink has a sign posted above it stating, "HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED." Reference: Section 1003.3, IPC 2018, as amended by the City of Tucson.
5. Revise the gas diagram to show the coffee roaster, D24, with an input of 140 MBH and the branch piping at 1" instead of ¾". Reference: Section 402.1, IFGC 2018.
6. The branch gas piping serving the existing AC unit (150 MBH @ 96 feet DL) is undersized, it should have a 1" supply. Reference: Section 402.1, IFGC 2018.
11/10/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide additional information from the roaster manufacturer regarding the vent for the coffee roaster: vent materials, positive or negative pressure venting, clearance from combustibles, chaff control, etc. Reference: Sections 301 and 304.1, IMC 2018.
2. Provide additional information from the wood-fired pizza oven manufacturer regarding the installation and maintenance of a chimney to vent the oven. Reference: Sections 301 and 304.1, IMC 2018.
11/10/2020 ROBERT SHERRY WATER REVIEW Completed
11/13/2020 DTRAMME1 ENGINEERING REVIEW Passed
11/19/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Show locations of light switches in the remodeled restrooms.
2. Provide GFI protection for the receptacles in the kitchen and food prep areas. NEC 210
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.
11/30/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/30/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/02/2020 NICHOLAS ROSS ZONING REVIEW Approved