Permit Number: T20CM07343
Parcel: 114469500

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM07343
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/27/2020 DTRAMME1 ENGINEERING REVIEW Passed
10/29/2020 JPEELDA1 FIRE REVIEW Approved
11/12/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Edit the equipment descriptions in the gas meter load table. Reference: Section 107.2.1, IBC 2018
11/12/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
11/12/2020 ROBERT SHERRY WATER REVIEW Completed
11/18/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Ref; Plan Sheet E3.0. Show size and rating of the OCPD in the Electrical Service Panel feeding the new panel 'D'.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.
11/30/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/30/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/17/2020 STEVE SHIELDS ZONING REVIEW Approved