Review Details: COMMERCIAL - TI

Permit Number - T20CM07333
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/13/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The restroom still opens directly into a food preparation area. [Initial comment: Per Section 403.3.2, IPC 2018, toilet rooms shall not open directly into a room used to prepare food for public service.]
01/13/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The proposed walk-in cooler does not have display doors. See Table C403.10.2.1 (3), IECC 2018 and just consider the indoor system of the appropriate capacity (i.e. 9,000 BTUH or less or greater than 9,000 BTUH). [Initial comment: Show that the walk-in cooler meets the efficiency requirements of Section C403.10.2.1, IECC 2018.]
01/14/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Per the previous electrical plan review comment #1," Ref; Electrical Plan Sheet E2.
(a) Provide a legend on the electrical plans that correlates with the encircled numbers pointing to the electrical devices."
The added Kitchen Legend refers to plan sheet A1.1. This plan sheet could not be located in the submitted plan set. Please clarify.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.
01/19/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved