Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM07333
Parcel: 12212010B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM07333
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/27/2020 DTRAMME1 ENGINEERING REVIEW Passed
10/29/2020 JPEELDA1 FIRE REVIEW Approved
11/12/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Per Section 403.3.2, IPC 2018, toilet rooms shall not open directly into a room used to prepare food for public service.
2. Hand sinks (12) in the kitchen are allowed to connect to the sanitary waste system instead of the grease waste system only if each sink has a sign posted above it states, "HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED." Reference: Section 1003.3, IPC 2018, as amended by the City of Tucson.
3. Correct the total load and total developed length notes on the gas diagram, C/P3. Provide the developed pipe length for the branch serving the existing AC units. Reference: Section 107.2.1, IBC 2018.
11/12/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Show that the walk-in cooler meets the construction requirements of Section C403.10.2, IECC 2018.
2. Show that the walk-in cooler meets the efficiency requirements of Section C403.10.2.1, IECC 2018.
3. Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.2.4, IMC 2018 (the hood hanging weight plus the weight of personnel working in or on the hood). Reference: Section 302.1, IMC 2018.
4. Show that the hood installation complies with Section 507.2.6, IMC 2018 for clearances.
11/12/2020 ROBERT SHERRY WATER REVIEW Completed
11/18/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Ref; Electrical Plan Sheet E2.
(a) Provide a legend on the electrical plans that correlates with the encircled numbers pointing to the electrical devices.
(b) Provide for GFI protected receptacles in the kitchen and food prep areas. NEC 210.8B(2).
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.
11/30/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1 (Code Analysis); Sheet A3 (Floor Plan): The Code Analysis indicates 5 water closets + 1 urinal, while the plan indicates 4 water closets and 1 urinal. Please verify.
2. Sheet A1 (Code Analysis); Sheet A3 (Floor Plan): The Code Analysis indicates a total occupant load of 150. Per the IBC Table 1004.5, occupants must be added for commercial kitchens and storage spaces. Please verify and revise the total occupant load as required.
3. Sheet A1; Code Analysis (Plumbing Fixtures): Please indicate on this sheet the required plumbing fixture calculations per the IBC Section 2902.1.1.
4. Sheet A2; Demolition Notes: Note 32 is indicated twice on the Demolition Plan. Please remove interior Note 32.
5. Sheet A2; Demolition Plan: Please add a north arrow to the plan.
6. Sheet A3; Fixed Seating Count Table: The Table indicates 4-six seat tables in the new space, but only indicates 3 on the Plan. Please verify.
7. Sheet A5; Reflective Ceiling Notes: Note 5 was not located on the Plan. Please verify.
8. General: Please provide written responses to all review comments.
12/10/2020 SAMUEL ROGERS ZONING REVIEW Approved
12/10/2020 SROGERS2 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed