Parcel: 136092110

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM07322
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T20CM07322
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

STRUCTURAL PLANS:

1. Provide an engineer’s calculation, design and seal for retaining walls with unbalanced fill exceeding 48 inches or a 24 inch retainer supporting a wall, R404.4. The retainer wall depth is measured from finished grade to bottom of foundation.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Show the “R” values of insulation for the O.H. Garage doors, N1102.1.

Please contact the plans reviewer if you have any questions:
Ken Van Karsen
(520) 837-4912 PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review
04/26/2021 STEVE SHIELDS ZONING REVIEW Approved
04/28/2021 JPEELDA1 FIRE REVIEW Approved