Permit Number: T20CM07322
Parcel: 136092110

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM07322
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/05/2020 SBLOOD1 ENGINEERING REVIEW Passed
11/10/2020 ANDREW CONNOR NPPO REVIEW Passed
11/19/2020 SAMUEL ROGERS ZONING REVIEW Reqs Change FROM: Samuel Rogers
PDSD Zoning Review Section

PROJECT: T20CM07322
Carport Conversion and Garage (1st Review)
2291 S Reflection Vista Pl

TRANSMITTAL DATE: 11/19/2020

DUE DATE: 11/09/2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


01. COMMENT: Per UDC 6.6.3.D - The total gross floor area (gfa) of all accessory structures shall not exceed 50% of the gfa of the principal structure (includes any attached covered porches). The proposed structure (2893-sf) appears to exceed 50% of the GFA of the principle structure (2896.5. Either revised the size of the structure or connect the structure to the main residence.


02. COMMENT: Per UDC 6.6.3.D - Accessory structures shall not exceed 12 feet in height, unless attached to a principal structure. If attached to the principal structure, maximum height permitted shall be the same as for the principal structure. Either revised the height of the structure or connect the structure to the main residence.


03. COMMENT: Several required elements are missing from the site/plot plan (lot coverage, adjacent zoning). For zoning/plot plan requirements see: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf



If you have any questions about this transmittal, Contact Samuel Rogers at Samuel.Rogers@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans
11/30/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change PROVIDE A COMPLETED PLAN SET FOR 2018 IRC COMPLIANCE REVIEW WITH WALL SECTION, ROOF FRAMING AND ELECTRICAL SHEETS.