Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T20CM07257
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/05/2020 | SBLOOD1 | ENGINEERING | REVIEW | Approved | |
| 11/05/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 11/19/2020 | PC_JEDER1 | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/19/2020 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 12/03/2020 | SAMUEL ROGERS | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/08/2020 | PCAMARE1 | OUT TO CUSTOMER | Completed |