Permit Number: T20CM07251
Parcel: 111053800

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM07251
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/04/2020 SBLOOD1 ENGINEERING REVIEW Passed
11/05/2020 ANDREW CONNOR NPPO REVIEW Passed
11/23/2020 STEVE SHIELDS ZONING REVIEW Reqs Change FROM: Steve Shields
Section Manager

PROJECT:
T20CM07251
3103 N Needham Place
Rear Porch Addition

TRANSMITTAL: November 23, 2020
This site is located in the R-2 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6, .9, & .10.

1. Provide a fully dimensioned elevation of the porch so that perimeter yard setback requirements can be verified. It appears that a Design Development Option (DDO) will be required to reduce the perimeter yard setback for the porch.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A).

2. Per UDC Article 6.4.5.D.1 a roof overhang may only encroach into an interior property line perimeter yard setback 2’-0”.
11/25/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Completed