Permit Number: T20CM07250
Parcel: 125075510

Address:
2245 E 8TH ST

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T20CM07250
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/21/2021 AWARNER1 NPPO REVIEW Passed
07/28/2021 PCAMARE1 ENGINEERING REVIEW Passed
08/02/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Completed
08/06/2021 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T20CM07250
2245 E 8th St – R-1
Master Bedroom & Laundry Addition (1st Revision)

TRANSMITTAL DATE: August 6, 2021

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

1. Based on the changes to the elevations it does not appear that the master Bedroom additions meets perimeter yard setbacks to the west property line.

Perimeter yard setbacks are based on a measurement from design grade to the highest point of the wall, see Unified Development Code (UDC) Article 6.4.5.b & Figure 6.4.5-A.


COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A).

2. Based on a wall height of 14’-0” the required perimeter yard setback to the west property line is 9’-5”, proposed setback is 8’-2”. A Design Development Option (DDO) will need to be submitted and approved prior to the approval of this plan revision. DDO requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf. A DDO is a separate submittal from the building plan and shall be submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using the Submission Type “Zoning Administration”. If you have questions about the DDO application or process please contact Mark Castro at Mark.Castro@tucsonaz.gov.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
08/06/2021 NGARCIA3 OUT TO CUSTOMER Completed