Permit Number: T20CM07230
Parcel: 12417157B

Address:
1050 E 19TH ST

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T20CM07230
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/04/2020 JPEELDA1 FIRE REVIEW Approved
11/04/2020 SBLOOD1 ENGINEERING REVIEW Approved
11/05/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Ref; Electrical line drawings. The configuration of the transfer switches shows both normally closed and normally open both open at the same time. Please revise to show the proper position.
2. Please indicate to correct sequence of operation on the plans.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.
11/23/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/02/2020 STEVE SHIELDS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/07/2020 IMONSHI1 OUT TO CUSTOMER Completed