Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T20CM07215
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/10/2020 | NMARTEL1 | ZONING | REVIEW | Approved | |
| 11/16/2020 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
| 11/25/2020 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | T20CM07215 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL COMMENTS: 1. A special inspection request is required with the permit application for epoxy setting as shown on detail #2/A2, R109.2. SITE PLAN: 1. Indicate the location and size of the water line from property line (meter) to building, R106.1.1. Show an existing or upgraded 1” line to the water heater. Minimum size for a two bathroom building is usually 1”, P2903.7. FLOOR PLANS: 1. Provide a landing with minimum 36” depth between the door and tread at the exterior doorway, R311.3. SECTIONS - DETAILS: 1. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38. MECHANICAL PLANS: 1. Provide demand calculations in accordance with Manual J standards, M1401.3, M1601.1. Notate if the mechanical system calculations may be provided by deferred submittal. ELECTRICAL PLANS: 1. Provide a panelboard clear working space of 30”wide x 36”deep, E3405.2. An appliance may not block unobstructed access to the panel. 2. Show receptacle outlets at wall spaces 2’ or more with no wall point (exclude door openings) more than 6’ from a receptacle outlet, E3901.2. Add appropriate outlets. 3. Show at least one wall switch controlled light outdoor entrances, E3903.3. 4. Specify high-efficacy lamps for at least 90% of all lighting fixtures, N1104.1. Update note #1. If you have any questions, please contact: Ken Van Karsen (520) 791-5550 City of Tucson Residential Plan Review |