Permit Number: T20CM07209
Parcel: 11714396D

Address:
615 S 9TH AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM07209
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/08/2021 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T20CM07209
615 S 9th Ave. – HC-3
New SFR
Residential (2nd Review)

TRANSMITTAL DATE: July 8, 2021

COMMENTS: the following comments are relative to an application for Historic Review (UDC 5.8.8).


This site is located in the HC-3 zone (UDC 4.7.22). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-4).

1. Zoning acknowledges that an agreement was provided with this submittal. This agreement has not been fully executed and must be recorded prior to approval of this plan.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov
07/08/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T20CM07209 R1
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL COMMENTS:

1. The gray water Ordinance #10579/11089 was revised to eliminate a gray drain line from various fixtures which potentially depleted black drain flow. Consider removal of the gray drain line throughout the building. Furthermore, remove the gray water discharge from the clothes washer which is located within 5 feet from the property line. The gray water discharge is not required if a line to the Garden Court is not feasible.

SECTIONS - DETAILS:

1. Show a roof design with insulation types for meeting the condensation control requirement and the minimum total insulation value of R-38 (Two layer system). Consider adding a layer of batt insulation (R-8 foam plus R-30 batt) or increase the amount of spray foam from the minimum R-5 to total requirement of R-38 (One layer system).

ELECTRICAL PLANS:

1. Protection of all interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors requires combination type arc-fault circuit interrupters, E3902.16. Update note #30 with the deletion of “installed in bedrooms”.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to sheet M1.01.