Review Details: RESUBMITTAL

Permit Number - T20CM07180
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/09/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Roof projections may not extend to a point closer than 2 feet from the property line, R302.1 Update Sheet #3 showing 1'-6"

A special inspection request is required with the permit application for welding, R109.2. See
https://webcms.pima.gov for a list of inspectors.
03/15/2021 STEVE SHIELDS ZONING REVIEW Reqs Change FROM: PDSD Zoning Review


PROJECT:
T20CM07180
150 S Cuesta Ave
Carport Addition
Residential (1st Review)


TRANSMITTAL: March 15, 2021
COMMENTS: The following comments are for the purpose of applying for a variance before the Board of Adjustment (UDC Section 3.10.1).

This site is located in the R-2 zone (UDC 4.7.9). A Duplex is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6, .9, & .10.

1. Sheet 3 and sheet 7 show different perimeter yard setback dimensions and until clarified Zoning cannot provide the required comments to process the required Board of Adjustment for Variance.

2. As you are showing an encroachment into the street right-of-way along S. Silverbell Ave you will need to contact COT Department of Transportation and Mobility and request permission for the encroach. A Temporary Revocable Easement may be required. Contact Zelin Canchola at Zelin.Canchola@tucsonaz.gov. Written permission shall be provided with your next submittal.