Permit Number: T20CM07141
Parcel: 123050300

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM07141
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/20/2020 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Section Manager

PROJECT: T20CM07141
2126 E Juanita Street
Attached Work Shop
Residential (1st Review)

TRANSMITTAL DATE: October 20, 2020

This site is located in the R-1 zone (UDC 4.7.8).

COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

Per UDC Article 6.4.5.B.1 & Figure 6.4.5-A the perimeter yard setback is based on the highest point of the wall measured to design grade

1. Based on a wall height of 12’-0” the required perimeter yard setback from the proposed attached work shop to the east property line is 8’-0”, proposed perimeter yard setback is 4’-8”. A Design Development Option (DDO) must be submitted and approved for the reduced perimeter yard setback prior to approval of these plans. You can find the DDO requirements at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
10/20/2020 SSHIELD1 ENGINEERING REVIEW Passed
10/20/2020 SSHIELD1 NPPO REVIEW Passed
11/16/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change PROVIDE A COMPLETE PLAN SET FOR REVIEW.