Permit Number: T20CM07124
Parcel: 117070800

Address:
528 S HERBERT AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM07124
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/02/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Provide a single plan set of all sheets with an engineer’s calculation, design and seal for a performance design when minimum sizes are not code compliant with the 2018 IRC, R301.1.
12/22/2020 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: Steve Shields
Section Manager

PROJECT:
T20CM07124
528 S Herbert Ave
Room Addition (2nd Review)

TRANSMITTAL: December 22, 2020
COMMENTS: the following comments are relative to an application for Historic Review (UDC 5.8.8).

This site is located in the HR-3 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A). Based on a wall height of 12’ the required perimeter yard setback from the proposed addition to the north and south property line is 8’-0”. Proposed perimeter yard setback to the north property line is 6’-6” and to the south property line is 4’-6”. Historic review is required to reduce perimeter yard setbacks.