Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T20CM07031
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/14/2020 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
10/14/2020 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
10/14/2020 | SSHIELD1 | NPPO | REVIEW | Passed | |
10/28/2020 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Completed |