Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T20CM06960
Review Name: OTHER
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/13/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The plans show a 1" water meter serving a total of 720 fixture units which equates to a demand of 164 GPM. A 1" water meter is limited to a maximum demand of 50 GPM; this installation will require a 3" water meter based on the current policy of Tucson Water. 2. The plans show three branches to distribute water to the mobile home park. With a maximum water velocity of 8 feet per second, 2" Schedule 40 PVC can handle only 84 GPM. Provide a breakdown of the fixture units for each section of the mobile home park and determine the required pipe sizes for the water mains serving each of the three branches. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/03/2020 | PCAMARE1 | OUT TO CUSTOMER | Completed |