Permit Number: T20CM06945
Parcel: 115050690

Address:
214 W SAHUARO ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM06945
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/28/2020 SAMUEL ROGERS ZONING REVIEW Reqs Change From: Samuel Rogers, Planner
PDSD Zoning Review

PROJECT: T20CM06945; Porch Addition and Interior Remodel
Building Plans (2nd Review)
214 W Sahuaro St – O-3 Zone

TRANSMITTAL DATE: December 28, 2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review comments were addressed.

The setback to the east property line is required at 10 ft or ¾ the wall height, whichever is greater. The proposed setback on the east site is 6’. Either the setback will need to be revised or a Design Development Option (DDO) may be pursued.
A DDO may offer approval if the proposed setback is a minimum of 1 ft from property line. Additional information regarding the DDO process can be found online here: www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf


If you have any questions about this transmittal, please contact me at Samuel.Rogers@tucsonaz.gov.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: revised plot plan