Permit Number: T20CM06886
Parcel: 13313005E

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T20CM06886
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/08/2020 KROBLES1 COMMUNICATIONS REVIEW Passed
10/28/2020 JPEELDA1 FIRE REVIEW Approved
10/29/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. The submitted documents were marked up and paragraphs partially lined out. Please submit complete documents.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.
11/16/2020 SBLOOD1 ENGINEERING REVIEW Passed
11/18/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: Please provide drawings for the new mounting and antenna framing. These drawings must be stamped, signed, and dated by a registered design professional.
2. General: Please provide structural calculations for the new mounting and antenna, along with the adequacy of the existing tower. These calculations must be stamped, signed, and dated by a registered design professional.
3. General: Please provide a site plan indicating the location of the cell tower.
4. General: Please provide a valuation (labor + materials) for this permit.
11/19/2020 STEVE SHIELDS ZONING REVIEW Approved
11/19/2020 STEVE SHIELDS PLANNING-CITY HALL REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
11/25/2020 PCAMARE1 OUT TO CUSTOMER Completed