Permit Number: T20CM06882
Parcel: 13608032A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM06882
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/21/2020 JVINCEN1 FIRE REVIEW Approved
10/29/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
10/29/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
10/29/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/29/2020 ROBERT SHERRY WATER REVIEW Passed
11/02/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
11/02/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet 1G01.02; Plan Review Data: The Project Information indicates 45,000 SFMedical Office Building, while the Building Design Data indicates 46,760 SF. Please coordinate.
2. Sheet 1S1.00; Structural Notes (Codes and Standards): Please remove the 2012 IBC reference.
3. Sheet 1S1.00; Structural Notes (Foundations): Note 1 indicates a soils report was used in this project design. Please provide that report for review.
4. Structural Calculations; Building Codes: Please remove the 2012 IBC reference.
5. General: Please provide north arrows on Sheeets 1G02.01, 1G02.02, 1A01.01, 1A01.02, 1A01.03, 1S1.01, 1S1.02, and 1S2.01.
6. General: Please provide a Special Inspection Certificate with Parts A and B completed. This form may be found at www.tucsonaz.gov/PDSD.
7. General: Please remove all references to the 2012 IBC.
8. General: Please provide written responses to all review comments.
11/16/2020 SBLOOD1 ENGINEERING REVIEW Approved
11/19/2020 STEVE SHIELDS ZONING REVIEW Approved