Permit Number: T20CM06846
Parcel: 117143200

Address:
575 S MAIN AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM06846
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/06/2020 ANDREW CONNOR NPPO REVIEW Passed
10/06/2020 DTRAMME1 ENGINEERING REVIEW Passed
10/15/2020 SAMUEL ROGERS ZONING REVIEW Reqs Change FROM: Samuel Rogers – Planner
PDSD Zoning Review Section

PROJECT: T20CM06846
New SFR (1st Review)
575 S Main Av

TRANSMITTAL DATE: 10/15/2020

DUE DATE: 9/28/2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


01. COMMENT: The gross floor area (GFA) of all accessory structures (existing adobe, building 2) cannot exceed 50% of the GFA of the primary structure (building1). Revise plans on the next submittal.

If building 1 were attached to building 2 by a 5' connection with a 20-pound live load building 1 and 2 will be considered one structure.


If you have any questions about this transmittal, contact Samuel Rogers at Samuel.Rogers@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans
10/15/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T20CM06846
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

SITE PLAN:

1. Show compliance with the Pool Barrier requirement by including a pool alarm system for doors and windows open to the pool, or show a continuous barrier around the pool, 2018 ISPSC. This is required with the pool permit.

FOUNDATION PLANS:

1. The pool permit will require an engineer’s calculation for foundation wall reinforcing when placed closer than 4 feet to the building, R404.1.1.

SECTIONS - DETAILS:

1. Clarify keynote 7.04 shown at the roof level on sheet A3.10, R106.1.1.

PLUMBING PLANS:

1. Show gas pipe sizes in compliance with connected demand, G2413.3 & Table G2413.4(1). Provide a gas line isometric or table for showing the BTU demand and length of line to each gas appliance. Pipe D at 1” will not serve the total demand if the developed length exceeds 40 feet.

ELECTRICAL PLANS:

1. Smoke alarms are required outside each separate sleeping area, R314.3.2. Show a smoke alarm in each bedroom and outside in the immediate vicinity of the lower floor bedrooms.
2. Clothes Washer and Dishwasher GFCI: receptacles require readily accessible protection typically from an upstream device, E3902.9 & 10. Add notation to plans.
3. Protection of all interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors requires combination type arc-fault circuit interrupters, E3902.16.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to plans.

If you have any questions, please contact:
Ken Van Karsen
(520) 791-5550
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/20/2020 VFLORES1 APPROVAL SHELF Completed
10/20/2020 VFLORES1 OUT TO CUSTOMER Completed
10/20/2020 VFLORES1 REJECT SHELF Completed