Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T20CM06844
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/21/2020 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 10/21/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Faucets serving lavatories in all buildings other than R3 occupancies, individual units in R2 occupancies, or International Residential Code structures shall be automatic faucets dispensing a maximum of 0.25 gallons per cycle. The cycle time shall not be less than ten-seconds for accessibility. Reference: Section 419.6, IPC 2018 as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 2. A common vent is limited to serving two traps or trapped fixtures (e.g. the lavatories in the men's and women's restroom). Reference: Section 911.1, IPC 2018. |
| 10/21/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 10/21/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 10/21/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Demonstrate energy code compliance for the building envelope using calculations based on the current code. Reference: Sections C101.5, C103.2, C303, and C401.2, International Energy Conservation Code 2018. 2. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation. Reference: Section C103.2, IECC 2018. |
| 10/26/2020 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: Steve Shields Section Manager PROJECT: T20CM06844 Oasis Church @ Rita Ranch 9021 S Atterbury Wash Way TRANSMITTAL DATE: October 26, 2020 DUE DATE: October 26, 2020 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. Zoning cannot approve the building plans until all other PDSD review agencies have approved. 2. Development Package DP19-0146 must be issued prior to issuing this building permit. If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package |
| 11/09/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A2; Floor Plan: The building section A5/A9 should be cut looking east, or that section should be reversed. Please verify. 2. Sheet A2; Floor Plan: Please cut building section A2/A9 on this Floor Pllan. 3. Sheet A2; Floor Plan: An enlarged detail at the podium references Detail 'J' on Sheet A9. Please revise that reference. 4. Sheet A6; Key Notes: Notes 5 and 6 were not located on the Roof Plan. Please verify. 5. Sheet A14; Typical Shower Detail 3D: Please indicate and dimension the transfer type shower grab bars per the ICC/ANSI Section 608.3.1.1 and 608.3.1.2. 6. Sheet A14; Typical Shower Detail 5A: Please indicate and dimension the grab bars for the accessible shower. 7. Sheet S1.0; Structural Notes (Foundations): Notes 1, 2, and 3 reference a geotechnical report. Please provide that report for review. 8. General: Please provide a Special Inspections Certificate with Parts A and B completed. 9. General: Please provide written responses to all review comments. |
| 11/09/2020 | SBLOOD1 | ENGINEERING | REVIEW | Approved | |
| 11/09/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/12/2020 | IMONSHI1 | OUT TO CUSTOMER | Completed |