Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM06834
Parcel: 13309064A

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T20CM06834
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
10/05/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
10/05/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet TS1.0; Code Study (Area): Please provide the actual gross area and allowable area in this Code Study. Separate Building A from Building B for total area and total occupant load.
2. Sheet TS1.0; Code Study (Occupant Loads): Please provide the Occupancy Use, Area, Factor, and Occupancy Load in this Code Study, along with the number of exits and exit widths required. Separate Building A from Building B for total area and total occupant load.
3. Sheet TS1.0; Allowable Area Calculation: This Table references Sheet A0.1 for a detailed summary. Please revise the sheet reference.
4. Sheet TS1.1; Plan: Please indicate "Existing" in the Building A Storage and Entry areas. Indicate "Existing" in the Building B Store and Entry areas.
5. Sheet TS1.0; Project Plumbing Fixture Calculations: Please indicate how the total existing occupant load of 1559 was determined.
6. Sheet S1.0; General Structural Notes (Foundations): Note 1 indicates a soils report was used for the foundation design. Please provide that report.
7. General: Please provide a Special Inspections Certificate with Parts A and B completed.
8. General: Please provide written responses to all review comments.
10/06/2020 ROBERT SHERRY WATER REVIEW Completed
10/07/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units, AC-1 and AC-2. Reference: Section C403.1.1 and C502.2.3, IECC 2018.
10/07/2020 SBLOOD1 ENGINEERING REVIEW Reqs Change 1. Proposed work doesn't match previous approved development plan DP14-0200. Please provide updated version.
10/07/2020 JPEELDA1 FIRE REVIEW Reqs Change Gift Store main doors shall comply with 2018 IFC 1010.1.2.1 Direction of swing. Please correct on the drawings. Also, I believe that there is a fire alarm in Building B. What is the combined new occupant load for Building B, I did not see that on the plans. If you will be extending the fire alarm place a note on the cover sheet stating that the fire alarm is a deffered submittal.
10/07/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide secondary (overflow) roof drainage for the area north of the ridgeline over the new storage room. Reference: Sections 1108.1, 1108.2 and 1108.3, IPC 2018.
10/15/2020 NMARTEL1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL
Nicholas Martell, Planner
T20CM06834
8005 E Speedway
Commercial Expanion
Transmittal Date: October 15, 2020

The expansion plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

1. The project is an expansion of a commercial site, triggering a Development Package. This project cannot be reviewed until it is submitted as a Development Package. For instructions on how to submit a DP, follow the links provided.

Application: https://www.tucsonaz.gov/files/pdsd/forms/Development_Package_and_Land_Division-Subdivision_Application.pdf

Instructions: https://www.tucsonaz.gov/pdsd/apply-permit#Development%20Package

For reference, a Development Package was done on the property in 2014 (DP14-0200).

Ensure the rezoning procedures found on activity number C9-08-05 are addressed on the Development Package upon submittal.



If you have any questions about this transmittal, please contact me at Nicholas.Martell@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
10/26/2020 PCAMARE1 OUT TO CUSTOMER Completed