Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T20CM06822
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/06/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
10/06/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
10/06/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | Please address the following electrical plan review comments. Also provide a written response. 1. Ref; Plan Sheet 16 of 25. (a) Provide for a Grounding Electrode System or a grounding detail, and how it connects to the building ground grid. A concrete encased electrode installed in the concrete footing is mandatory in new building construction per NEC 250.52(3). Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
10/06/2020 | ROBERT SHERRY | WATER | REVIEW | Passed | |
10/06/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet 1S1.00; Structural Notes (Codes and Standards): Note 1 indicates the 2012 and 2018 IBC. This project should be under the 2018 IBC only. Please verify. 2. Sheets 1S1.01, 1S1.02, and 1S2.01; Plans: Please add north arrows to all plans. 3. Structural Calculations; Page 1 (Building Codes): A note indicates the 2012 and 2018 IBC. This project should be under the 2018 IBC only. Please verify. 4. General: Please provide a Special Inspections Certificate with Parts A and B completed. This form may be found at www.tucsonaz.gov/PDSD. 5. General: Please provide written responses to all review comments. |
10/06/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
10/09/2020 | ALEXANDRA HINES | ZONING | REVIEW | Reqs Change | RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Please resubmit updated drawings along with a detailed comment response letter, which states how all zoning review comments were addressed. 1. COMMENT: Zoning has reviewed the building plans for compliance with the unapproved development package (DP19-0069) and found that the building plans are consistent with the unapproved development package as it relates to the zoning requirements, which includes the building square footage, building height, building footprint, and location on the site. 2. COMMENT: Zoning will review the building plans on the next submittal to assure that any updates made to the building plans or the development package does not affect zoning requirements. 3. COMMENT: Zoning cannot approve the building plans until all PDSD commercial plans reviewers have also approved the building plans. If you have any questions about this transmittal, Contact Alexandra Hines at alexandra.hines@tucsonaz.gov. |
10/16/2020 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
10/28/2020 | JPEELDA1 | FIRE | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/02/2020 | PCAMARE1 | OUT TO CUSTOMER | Completed |