Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM06778
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/05/2020 | JPEELDA1 | FIRE | REVIEW | Reqs Change | Door shall open in the direction of travel Code reference sheet and drawings that are not stamped shall be submitted. This is a change of occupancy house to a M occupancy. All current M requirements shall be shown that they are met. |
| 10/15/2020 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 10/15/2020 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 10/15/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
| 10/22/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The last Certificate of Occupancy for this address was a mercantile occupancy. Changing to a tattoo studio (business occupancy) is a change of occupancy and will require the submission of drawings to show that the suite meets the current code requirements for the new occupancy. The drawings must be produced by an Arizona registrant (i.e. a licensed architect or engineer). |
| 10/22/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The last Certificate of Occupancy for this address was a mercantile occupancy. Changing to a tattoo studio (business occupancy) is a change of occupancy and will require the submission of drawings to show that the suite meets the current code requirements for the new occupancy. The drawings must be produced by an Arizona registrant (i.e. a licensed architect or engineer). |
| 10/22/2020 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Show the location of the reduced pressure backflow assembly on the drawings; indicate the size of the assembly. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf. |
| 11/04/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. General: Per the IEBC Section 506, changes in occupancy in a building shall be such that the existing building is not less complying with the provisions of this code than the existing building was prior to the change. The Occupancy Classification is changing from a residential single family residence (or from a retail store) to a commercial retail store (or a tattoo studio). The single restroom would meet the requirements of the IBC Section 2902.2(3), but would not meet the accessibility requirements of Section 1109.2. This would be an issue for the registered design professional to discuss and/or appeal with the Building Official. Please proceed as required. 2. General: The current drawing indicates a single family residence to a retail use. Is the existing use retail, and the new use B? Please clarify on the drawing, and revise the occupant load and required plumbing fixtures as required. This would also require a discussion for the registered design professional with the Building Official. 3. General: Please provide a written response to the review comments. |
| 11/04/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |