Permit Number: T20CM06743
Parcel: 208261050

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T20CM06743
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/29/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/29/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
09/29/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet 9 of 35; Foundation Plan: The column and footing note at each grid line indicates "? column and footing". Please revise that note.
2. Sheet 9 of 35; Drilled Shaft Foundation Enlarged Plan A: The note at each bolt line indicates "? bolt". Please revise that note.
3. Sheet 10 of 35; Roof Framing Plan: The column and beam note at each grid line indicate "? beam and column". Please revise that note.
4. Sheet 10 of 35; Framing Keynotes (2): This note references 4/S4 for the lifting lug detail. Please revise that reference.
5. Sheet 11 of 35; West and North Elevations: The note at each column, pier, and lug line indicate "? lifting plate, column, and footing". Please revise that note.
6. Sheet 15 of 35; Building Section C: Please indicate the maximum roof slab thickness on this section.
7. Sheet 30 of 35; Radio Antenna Details: Please provide structural calculations for the antenna foundation design.
8. General: Please provide written responses to all review comments.
09/30/2020 LOREN MAKUS ENGINEERING REVIEW Reqs Change Pima County flood hazard map shows this parcel within a sheet flood area. Confirm whether a floodplain use permit is required with Pima County Regional Flood Control District.
10/01/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
10/01/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
10/01/2020 JPEELDA1 FIRE REVIEW Approved
10/01/2020 ROBERT SHERRY WATER REVIEW Passed
10/08/2020 ELISA HAMBLIN ZONING REVIEW Passed Site is located in unincorporated Pima County. City of Tucson zoning standards do no apply.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/27/2020 PCAMARE1 OUT TO CUSTOMER Completed