Permit Number: T20CM06730
Parcel: 134010140

Address:
101 S BROWN ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM06730
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/09/2020 ANDREW CONNOR NPPO REVIEW Passed
10/22/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change PROVIDE A SPECIAL INSPECTION REQUEST FORM FOR WELDING
10/26/2020 ALEXANDRA HINES ZONING REVIEW Reqs Change 1. Building (A, B, and shed) does not meet minimum required setback, 25 ft from property line in SR zone. a. Redesign or b. obtain approved DDO.
b. The following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1). This site is located in the SR zone (UDC 4.7.6). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-3). The minimum setback is twenty-five (25) feet facing each interior property line (Table 6.3-1.A). The proposed setback is twenty-two (22) feet facing the north property line.

Since buildings are all attached to principal structure, the buildings can run on one (1) permit, if desired request withdrawal of one permit. Currently, separated into two (2) permits. See T20CM06730 and T20CM06731.

Alexandra Hines
alexandra.hines@tucsonaz.gov
10/26/2020 LOREN MAKUS ENGINEERING REVIEW Passed