Permit Number: T20CM06702
Parcel: 116093700

Address:
3124 W ANKLAM RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM06702
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/21/2021 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T20CM06702
3124 W Anklam Rd
New SFR (1st Revision)

TRANSMITTAL DATE: October 21, 2021

This site is located in the RX-2 zone (UDC 4.7.7). A single-family residence is a permitted use in this zone (Table 4.8-1.

1. This comment was not addressed. Zoning acknowledges that this comment should have been made on the 1st review but a grading plan is required, see Engineering comments.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
10/29/2021 SBLOOD1 ENGINEERING REVIEW Reqs Change This project is located in the Hillside development zone and a grading development package is required. The grading plan needs to include but not limited to: the top and toe of slopes, pad elevation, show areas that can be developed, show natural undisturbed open space. Please reference plat S98-056.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
11/03/2021 JPEELDA1 FIRE REVIEW Reqs Change Meets the fire flow requirement per tucson water however the plans indicate fire sprinklers will be installed. Remove fire sprinkler notes from plans and include fire flow data/letter from tucson water.