Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM06702
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/21/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T20CM06702 3124 W Anklam Rd New SFR (1st Revision) TRANSMITTAL DATE: October 21, 2021 This site is located in the RX-2 zone (UDC 4.7.7). A single-family residence is a permitted use in this zone (Table 4.8-1. 1. This comment was not addressed. Zoning acknowledges that this comment should have been made on the 1st review but a grading plan is required, see Engineering comments. If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov. |
| 10/29/2021 | SBLOOD1 | ENGINEERING | REVIEW | Reqs Change | This project is located in the Hillside development zone and a grading development package is required. The grading plan needs to include but not limited to: the top and toe of slopes, pad elevation, show areas that can be developed, show natural undisturbed open space. Please reference plat S98-056. Stephen Blood (520) 837-4958 Stephen.blood@tucsonaz.gov |
| 11/03/2021 | JPEELDA1 | FIRE | REVIEW | Reqs Change | Meets the fire flow requirement per tucson water however the plans indicate fire sprinklers will be installed. Remove fire sprinkler notes from plans and include fire flow data/letter from tucson water. |