08/05/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T20CM06688
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

FLOOR PLANS:

1. Show one-hour fire-resistive framed construction in compliance with IBC Table 721.1(2). Detail or notate the method used for achieving the fire rating.

FRAMING PLANS:

1. Show the TJI roof joist size and series for determining performance compliance, R301.1

MECHANICAL PLANS:

1. Show dryer vent size and location for venting to exterior, M1501.

ELECTRICAL PLANS:

1. Provide a Riser Diagram with a single service panel and a sub-panel to the second building, E3607. Clarify the location of the property service meter and coordinate the utility plan with Tucson Electric Power.
2. Show at least one wall-switch-controlled lighting outlet providing illumination on the exterior side of each egress door having grade level access R3903.3.
3. Show or notate a disconnect means or a locking breaker for the water heaters, E4101.5.

OUTDOOR LIGHTING CODE

1. Show the proposed fixture as full cut-off FCO style or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
08/13/2021 STEVE SHIELDS ZONING REVIEW Approved
08/20/2021 JVINCEN1 FIRE REVIEW Approved