Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM06684
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/14/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
01/19/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed 01/19/21 - Sheet A3 revised to show a design for the fall protection railing.

01/14/21 - A quote of the relevant code section is not a design for the required guards on the roof. Provide a design. [Second comment: The architect needs to provide a design for the required guards on the roof. Reference: Section 107.2.1, IBC 2018.] [Initial comment: Provide guards for equipment located within 10 feet of a roof edge or of a walking surface that is elevated more than 30 inches above the adjoining grade. Reference: Section 304.11, IMC 2018.]