Permit Number: T20CM06684
Parcel: 12415016B

Address:
810 E 17TH ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM06684
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/15/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The architect needs to provide a design for the required guards on the roof. Reference: Section 107.2.1, IBC 2018. [Initial comment: Provide guards for equipment located within 10 feet of a roof edge or of a walking surface that is elevated more than 30 inches above the adjoining grade. Reference: Section 304.11, IMC 2018.]
12/15/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The manufacturer's specifications for the Garland model G60-4G36RR (Propane) show a total input of 262 MBH. If this is correct, the ¾" branch pipe is too small. What does the data plate on the appliance show for the total input? [Initial comment: Verify the connected load for the four appliances under the hood. The load on detail A/P1, the schedule on sheet A3, and the manufacturer's literature show different loads.]