Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM06684
Parcel: 12415016B

Address:
810 E 17TH ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM06684
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2020 JPEELDA1 FIRE REVIEW Approved
10/07/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Clarify keynote 8 on sheet P1; it calls for a ½" MP up to the ceiling but the schematic shows a ¾" MP at that location.
2. Verify the connected load for the four appliances under the hood. The load on detail A/P1, the schedule on sheet A3, and the manufacturer's literature show different loads.
10/07/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide guards for equipment located within 10 feet of a roof edge or of a walking surface that is elevated more than 30 inches above the adjoining grade. Reference: Section 304.11, IMC 2018.
2. Verify the listed exhaust flow rate for the hood for the proposed appliances. The code minimum exhaust flow rate for a wall canopy with heavy-duty appliances is 400 CFM/foot, twice what this hood is drawing. Reference: Sections 507.5 and 507.5.2, IMC 2018.
10/07/2020 ROBERT SHERRY WATER REVIEW Completed
10/14/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
10/15/2020 SSHIELD1 ENGINEERING REVIEW Passed
10/15/2020 STEVE SHIELDS ZONING REVIEW Approved
10/15/2020 DAN SANTA CRUZ BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A4: The stamp/signature/date of the registered design professional is required on this sheet.
11/03/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed