Permit Number: T20CM06675
Parcel: 14010029A

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T20CM06675
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/07/2020 ROBERT SHERRY WATER REVIEW Reqs Change 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304
2. Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf
3. Show the location of the proposed water meter, backflow preventer, and the water service pipe on a site plan. The development package is not a substitute for a complete site plan. Reference: Section 107.2.1 and 107.2.6, IBC 2018.
4. Provide the size of the water meter serving this building, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018.
10/08/2020 JPEELDA1 FIRE REVIEW Approved
10/14/2020 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Section Manager

PROJECT: Door Church Sanctuary
2950 E Irvington Rd
T20CM06675 (1st Review)


TRANSMITTAL DATE: October 14, 2020

1. Zoning has reviewed the building plans for compliance with the submitted development package, DP20-0093, but until the DP is approved Zoning cannot approved the building plan.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
10/29/2020 SBLOOD1 ENGINEERING REVIEW Reqs Change 1. Roof Plan A1.4 is missing from plan set

2. DP needs to be approved before building plans can be approved

Stephen Blood
stephen.blood@tucsonaz.gov
11/10/2020 STANTEC ELECTRICAL-COMMERCIAL REVIEW Completed
11/10/2020 STANTEC PLUMBING-COMMERCIAL REVIEW Completed
11/10/2020 STANTEC BUILDING-COMMERCIAL REVIEW Completed
11/10/2020 STANTEC MECHANICAL-COMMERCIAL REVIEW Completed
11/10/2020 ARUIZ1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/10/2020 ARUIZ1 OUT TO CUSTOMER Completed