Permit Number: T20CM06595
Parcel: 136129470

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM06595
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2020 SBLOOD1 ENGINEERING REVIEW Passed
09/24/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/24/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
09/24/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change The electrical line diagram shows the Branch Panels as existing. The Panel schedules shows them as New Panels, Please clarify.
Ref; 2018 IBC 107.2.1, 2017 NEC
09/24/2020 ROBERT SHERRY WATER REVIEW Completed
09/24/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/24/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide tempered water to the handwashing fixture using a mixing valve conforming to ASSE 1070. Reference: Sections 419.5 and 607.1.2, IPC 2018.
2. Verify that a cleanout is in place to serve the horizontal drain extending from the handwashing fixture and the drinking fountain. Reference: Section 708.1.1, IPC 2018.
3. Clarify how the waste and vent piping for the handwashing fixture and the drinking fountain are related. Will they be common vented? Reference: Section 107.2.1, IBC 2018.
4. Indicate the maximum distance from the hot water source (i.e. the recirculating hot water loop) and the handwashing fixture. Table C404.5.1, IECC 2018 limits the ¾" hot water branch to a maximum of 21-feet. Reference: Section C404.5.1, IECC 2018.
5. Revise the boxed note in the waste and vent schematic. The last sentence is not supported by Section 905.5, IPC 2018. If the fixture cannot be vented as shown in your schematic, revise your design to show how it is to be vented.
09/28/2020 JPEELDA1 FIRE REVIEW Approved
10/01/2020 ALEXANDRA HINES ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/30/2020 VFLORES1 APPROVAL SHELF Completed
10/30/2020 VFLORES1 OUT TO CUSTOMER Completed
10/30/2020 VFLORES1 REJECT SHELF Completed