| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/23/2020 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
| 09/24/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 09/24/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 09/24/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | The electrical line diagram shows the Branch Panels as existing. The Panel schedules shows them as New Panels, Please clarify. Ref; 2018 IBC 107.2.1, 2017 NEC |
| 09/24/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 09/24/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/24/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide tempered water to the handwashing fixture using a mixing valve conforming to ASSE 1070. Reference: Sections 419.5 and 607.1.2, IPC 2018. 2. Verify that a cleanout is in place to serve the horizontal drain extending from the handwashing fixture and the drinking fountain. Reference: Section 708.1.1, IPC 2018. 3. Clarify how the waste and vent piping for the handwashing fixture and the drinking fountain are related. Will they be common vented? Reference: Section 107.2.1, IBC 2018. 4. Indicate the maximum distance from the hot water source (i.e. the recirculating hot water loop) and the handwashing fixture. Table C404.5.1, IECC 2018 limits the ¾" hot water branch to a maximum of 21-feet. Reference: Section C404.5.1, IECC 2018. 5. Revise the boxed note in the waste and vent schematic. The last sentence is not supported by Section 905.5, IPC 2018. If the fixture cannot be vented as shown in your schematic, revise your design to show how it is to be vented. |
| 09/28/2020 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 10/01/2020 | ALEXANDRA HINES | ZONING | REVIEW | Approved |