Permit Number: T20CM06570
Parcel: 122154260

Address:
3308 E LINDEN ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM06570
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/02/2020 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Section Manager

PROJECT: T20CM06570
3308 E Linden St
Master Bed & Bath, Living & Carport Addition
Residential (1st Review)

TRANSMITTAL DATE: October 2, 2020

The room addition plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 – 9.

1. Provide a perimeter yard setback dimension from the post that support the proposed carport to the west property line.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
10/02/2020 SSHIELD1 NPPO REVIEW Passed
10/21/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T20CM06570
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans.

STRUCTURAL PLANS:

1. Provide a complete roof framing plan with rafters sized with appropriate load carrying capacity, R301.1. Include beam size and location.
2. Provide a header schedule and show opening sizes supporting new roof consistent with Table 502.5(1) & R602.7(1).

SECTIONS - DETAILS:

1. Update the cross-section detail of the new exterior wall on A-5, R106.1.1. Show exterior wood siding, sheathing and wall framing with a 6” clearance above the ground, R317.1 item 5. A concrete stem may be included if needed.
2. Specify all ledgers connected to masonry walls with 3x material, Figure R606.11 (1). Update detail
3. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing (closed cell spray or rigid board tight to the roof sheathing), R806.5. This condensation control provision is necessary for code compliance and may be a single layer of air-impermeable insulation or layered with batt insulation for achieving the total required roof R-value.

PLUMBING PLANS:

1. Clarify if the 1” water pipe between the meter and shut off valve in compliance with P2903.7 is existing or replaced.

ELECTRICAL PLANS:

1. Show or notate a disconnect means or a locking breaker for the water heater, E4101.5.

OUTDOOR LIGHTING CODE

1. Show the proposed fixture as full cut-off FCO style, or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing is U=0.40, skylights U=0.65, ceiling R=38 and framed walls R=13. Mass wall requirement is R=4 when 50% of insulation is exterior and R=6 when applied interior, N1102.1. Update details on A-5.

If you have any questions, please contact:
Ken Van Karsen
(520) 791-5550
City of Tucson Residential Plan Review
10/29/2020 SBLOOD1 ENGINEERING REVIEW Reqs Change 1. Property is within the floodplain. Floodplain Use Permit is required.

2. With the value of the property involved, a substantial improvement is being made and therefore requires an elevation certificate to show the finished floor elevation of both the proposed addition and existing structure to be 1' above the floodplain elevation

Stephen Blood
stephen.blood@tucsonaz.gov