Review Date Reviewer's Name Type of Review Description Status Comments
10/19/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide a plan with a complete line diagram, include: voltage, phase, AIC ratings of the equipment, feeder conduit and conductor sizes and types, location of the panel on the premises. Indicate whether new or existing for all the electrical equipment associated with the proposed new panel.
2. Resubmit.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.