Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T20CM06566
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/19/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide a plan with a complete line diagram, include: voltage, phase, AIC ratings of the equipment, feeder conduit and conductor sizes and types, location of the panel on the premises. Indicate whether new or existing for all the electrical equipment associated with the proposed new panel. 2. Resubmit. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/21/2020 | PCAMARE1 | OUT TO CUSTOMER | Completed |