Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM06542
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/22/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Passed
09/23/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Demonstrate energy code compliance for the alterations to the building envelope using calculations (e.g. COMcheck) based on the current code. Reference: Sections C103.2, C303, C503.1, and C503.3, International Energy Conservation Code 2018.
09/23/2020 SAMUEL ROGERS ZONING REVIEW Approved
09/23/2020 SBLOOD1 ENGINEERING REVIEW Passed
09/23/2020 SROGERS2 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/23/2020 ROBERT SHERRY WATER REVIEW Completed
09/24/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1.0; Code Review Checklist (General Building Summary); Reference Site Plan: The General Building Summary indicates the square footage of this space is 1730 SF, while the Reference Site Plan indicates 1324 SF. Please coordinate.
2. Sheet A2.0; New Steel Header Detail 1: In Keynote 3, please indicate the minimum lap length of the new reinforcing with the existing reinforcing.
3. General: Please provide a project valuation.
4. General: Please provide written responses to all review comments.
09/28/2020 JPEELDA1 FIRE REVIEW Approved
12/10/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed