Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM06542
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/22/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
09/23/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Demonstrate energy code compliance for the alterations to the building envelope using calculations (e.g. COMcheck) based on the current code. Reference: Sections C103.2, C303, C503.1, and C503.3, International Energy Conservation Code 2018. |
09/23/2020 | SAMUEL ROGERS | ZONING | REVIEW | Approved | |
09/23/2020 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
09/23/2020 | SROGERS2 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
09/23/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
09/24/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A1.0; Code Review Checklist (General Building Summary); Reference Site Plan: The General Building Summary indicates the square footage of this space is 1730 SF, while the Reference Site Plan indicates 1324 SF. Please coordinate. 2. Sheet A2.0; New Steel Header Detail 1: In Keynote 3, please indicate the minimum lap length of the new reinforcing with the existing reinforcing. 3. General: Please provide a project valuation. 4. General: Please provide written responses to all review comments. |
09/28/2020 | JPEELDA1 | FIRE | REVIEW | Approved | |
12/10/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed |