Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T20CM06507
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/21/2020 | DTRAMME1 | ENGINEERING | REVIEW | Passed | |
| 09/28/2020 | ANDREW CONNOR | NPPO | REVIEW | Passed | |
| 09/29/2020 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Section Manager PROJECT: T20CM06507 8171 E CRICKET SONG TR New SFR Residential (1st Review) TRANSMITTAL DATE: September 29, 2020 The room addition plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. This site is located in the C-2 zone (UDC 4.7.21). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-4). 1. Per UDC Article 6.4.5.C.2.b.(1) A minimum setback of 19 feet from the back of sidewalk to allow sufficient space for a motor vehicle to be parked in front of the carport or garage is required. The setback shown on the plan is from the back of curb. A Board of Adjustment for Variance is required. 2. Residential plot plan requirements can be found at https://www.tucsonaz.gov/pdsd/all-application-forms-submittal-requirements. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
| 10/09/2020 | AMARTIN1 | BUILDING-RESIDENTIAL | REVIEW | Needs Review |