Permit Number: T20CM06393
Parcel: 136253200

Address:
3331 S IRENE PL

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM06393
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/29/2020 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: Steve Shields
Site Section Manager

PROJECT:
T20CM06393
3331 S IRENE PL
New Guesthouse

TRANSMITTAL: September 29, 2020
COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10.

1. Per UDC Table 6.3-2.A: DIMENSIONAL STANDARDS FOR THE R-1, R-2, R-3, MH-1, & MH-2 ZONES, R-1 zone, minimum lot size for 2 dwelling unit is 10,000 sq. ft. As this parcel is less than 10'000 sq. ft a guesthouse is not allowed. A sleeping quarter with out a kitchen is allowed. For the proposed layout not to be considered a dwelling unit the double bowl sink must be removed and replaced with a single bowl bar type sink and the fullsize refrigerator replaced with an undercounter style refrigerator.

Per UDC Article 6.4.5.B and Figure 6.4.5-A perimeter yard setbacks are based on the highest point of the wall as measured from design grade.

2. The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A).
Based on a wall height of 9'-2" the required perimeter yard setback from the south wall to the south property lines is 6'-2". A neighbor perimeter yard setback waiver is required. Provide the following information on the plan for the neighbor to the south and have the owner sign and date:
"My Name is and I am the owner of the property located at . I have reviewed the site plan and I have no objection to structure being located or constructed from the property line as depicted on the site plan.
09/29/2020 SSHIELD1 ENGINEERING REVIEW Passed
09/29/2020 SSHIELD1 NPPO REVIEW Passed
10/15/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38. UPDATE DETAIL 3/A3.