Permit Number - T20CM06389
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/17/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G0.02; General Notes (1): This note references the 2015 Arizona Building Code with 2015 IBC amendments. Please revise those references to the 2018 IBC with amendments, and remove the 2015 ABC.
2. Sheet G0.02; General Notes (8b): This note references the 2014 Indiana Building Code. Please revise that reference.
3. Sheet G0.02; General Notes (14): This note references Sections 1012/1013, 1607.7, 1009.12, 1012.2 through 1012.9, and 1010.8. Please revise these references.
4. Sheet G0.02; General Notes (15): This note references ANSI A117.1-2003. Please revise that reference.
5. Sheet G1.01; Project Data (Project Description): Please revise this section.
6. Sheet G1.01; Project Data (Project Address): Please revise this section.
7. Sheet G1.01; Building Data (Building Description): Please revise this section.
8. Sheet G1.01; Building Data (Adopted Codes): Please revise this section as required for this permit.
9. Sheet A4.05; Enlarged Plan: This plan references the Pergola Plan to 1/A9.01-2. Please revise that reference.
10. Sheet A9.01; Proposed Pergola Plan: The section cuts 1/A9.02 and 2/A9.02 are reversed. Please verify.
11. Sheet A9.01; Proposed Pergola Plan: Please indicate the Elevations 1 and 2 on this plan.
12. General: Please provide a Special Inspection Certificate with Parts A and B completed. You can find this form at www.tucsonaz.gov/PDSD.
13. General: Please provide written responses to all review comments.
09/17/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide plans and evidence on the plans that the proposed exterior lighting fully complies with the Outdoor Lighting Code. See section 104 for plan submittal requirements.
2. Provide lighting plans with the following information on the plans;
(a) Provide a complete luminaire schedule.
(b) Size of the parcel in acres.
(c) See table 401.1, lighting area and option and indicate this information in the lighting site plan, also showing the locations and types of all exterior luminaires including existing.
(d) 402.1 (light source color temperature requirements), shielding requirements, etc .
(e) Provide calcs for total lumens allowed and total lumens proposed per acre including existing, for Full Cut Off and Unshielded per table 401.1.
(f) Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.
(g) Specify any exceptions used.
(h) Curfew lighting controls If applicable.
Do not confuse the Outdoor Lighting Code with the IECC.
Ref; 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code (OLC), 2018 IBC sec 107.2.1. 2018 IECC.
09/28/2020 JPEELDA1 FIRE REVIEW Reqs Change Sheet G1.01 has information for other Hub projects not this project. Sheets need to be corrected.
10/14/2020 STEVE SHIELDS ZONING REVIEW Approved
10/14/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
10/14/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed