Permit Number: T20CM06383
Parcel: 13502032A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM06383
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/17/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Locate the existing electrical service that feeds new panel 'L1' on the power plan.
Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.
09/17/2020 ROBERT SHERRY WATER REVIEW Completed
09/17/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change What is the purpose of the proposed sump pump installation? Reference: Section 107.2.1, IBC 2018.
09/17/2020 LOREN MAKUS ENGINEERING REVIEW Passed
09/17/2020 JPEELDA1 FIRE REVIEW Approved
09/18/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
09/23/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/23/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A-1.0; Code Review (Exit Travel Distance): The Sanctuary exit travel distance indicates a maximum actual distance of 135', while the Exiting Plan 3 indicates 185'-0". Please coordinate.
2. Sheet A-1.0; Code Review (Exit Travel Distance): The North, South, and East Buildings exit travel distance indicate a maximum actual distance of 109'-8", while the Exiting Plan 1 indicates 116'-6". Please coordinate.
3. Sheet A-1.0; Reference Site Plan: An enlarged detail references 14/A-6.0. Is that reference correct? Please verify.
4. Sheet A-1.0; Code Review (Plumbing Calculations): The calculations indicate 1446 occupants, while the occupant load calculation indicates 1449 (590 + 859). Please coordinate.
5. Sheet A-4.0; Roof Plan: Roof hatches are located on this plan in two separate locations. One hatch indicates Keynote 305, and the other hatch indicates Keynote 309. Please revise those Keynote references.
6. Sheet A-4.0; Roof Plan: Please indicate the distance on this plan of the roof hatch (Sount Building) to the exterior wall.
7. Sheet A-5.1; Detail 1: At the bracing for the interior partition, please indicate the size and quantity of connectors for the bracing to the partition and to the roof.
8. Sheet S4.0; Detail 107: Please provide a dimension (or add a reference) for the location of the epoxy bolt above the top of slab. Should Note 3 indicate concrete grout added to the existing masonry wall at the epoxy bolt locations?
9. General: Please provide a Special Inspection Certificate with Parts A and B completed. This form may be found at www.tucsonaz.gov/PDSD.
10. General: Please provide written responses to all review comments.
09/25/2020 MALLORY RESS ZONING REVIEW Reqs Change FROM: Mallory Ress
PDSD Zoning Review Section

PROJECT: T20CM06384 BLDG #1
Renovation of 4 buildings, excavation for drainage and add square footage (9.05% increase) (1st Review)
6620 E 22nd St
TRANSMITTAL DATE: 9/25/20

COMMENTS: A Development Package submittal is required for this project. The Building Permit cannot be issued until a Development Package has been issued.


01. COMMENT: Please submit a development package application. The requirements for a development package can be found here: https://www.tucsonaz.gov/files/pdsd/forms/Submittal_Requirements.pdf

02. COMMENT: Expansion calculation for all additions from last time site met full code compliance is required to be shown on the development package.

03. COMMENT: Include a parking calculation and demonstrate that parking requirements are met.


If you have any questions about this transmittal, Contact Mallory Ress at Mallory.ress@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Development Package