Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM06378
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/15/2020 | PIMA COUNTY | WATER | REVIEW | Reqs Change | 1. Response to previous review comment regarding the water meter is insufficient to show that the existing meter that serves all tenant spaces in this building is sized to accommodate the new load. Per the previous comment provide the size of the existing water meter and total water demand served by the water meter. |
| 12/15/2020 | PIMA COUNTY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 12/15/2020 | PIMA COUNTY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The walk-in cooler and freezer manufacturer's letter does not address the mandatory performance standards identified in Section C403.10.2.1, IECC 2018 which went into effect on January 1, 2020. Contact the manufacturer to resolve this issue. [Initial comment: Show that the walk-in cooler and freezer meets the efficiency requirements of Section C403.10.2.1, IECC 2018.] |
| 12/31/2020 | SAMUEL ROGERS | ZONING | REVIEW | Approved |