Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T20CM06378
Parcel: 141153570

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM06378
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2020 DTRAMME1 ENGINEERING REVIEW Passed
10/08/2020 JPEELDA1 FIRE REVIEW Approved
10/13/2020 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify the minimum gas pressure required for the specified fryers by the manufacturer. Southwest Gas, the local gas utility, provides natural gas at 7" WG, 2 PSIG, and 5 PSIG. Appliances needing gas service at 7" WG or greater will require a gas meter that delivers at least 2 PSIG gas into a regulator located after the meter set. Reference: Section 402.1, IFGC 2018.
2. If repair of the existing lavatory (keynote 1, P2.0) includes replacement of the faucet, a metering faucet will be required. Metering faucets shall dispense a maximum of 0.25 gallons per metering cycle and the faucet cycle shall last for at least 10-seconds for accessibility. Reference: Section 412.11, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
3. Hand sinks (S1) in the kitchen are allowed to connect to the sanitary waste system instead of the grease waste system only if each sink has a sign posted above it stating, "HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED." Reference: Section 1003.3, IPC 2018, as amended by the City of Tucson.
4. Provide a site plan showing the installation of the gravity grease interceptor. Reference: Section 107.2.1, IBC 2018.
10/13/2020 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the sequence of operation for the restroom exhaust fan, EF-3, so that all of the air supplied to the restroom will be exhausted (i.e. all of the air supplied to the restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Section 403.2.1 (4), IMC 2018.
2. Show that the walk-in cooler and freezer meets the construction requirements of Section C403.10.2, IECC 2018.
3. Show that the walk-in cooler and freezer meets the efficiency requirements of Section C403.10.2.1, IECC 2018
10/13/2020 PIMA COUNTY WATER REVIEW Reqs Change Provide the size of the water meter serving this suite, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018.
10/29/2020 MALLORY RESS ZONING REVIEW Reqs Change FROM: Mallory Ress
PDSD Zoning Review

PROJECT: T20CM06378
Restaurant-TI/Change of Use (1st Review)
8160 S Houghton RD Ste #100


COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review comments were addressed.
1. COMMENT: It appears that Sheet E4.0, notes A and B indicate that a drive-thru is proposed, however no other sheets depict this. If it is the case that a drive-thru is proposed a development package will be required. If a drive-thru is not proposed correct notes accordingly.

If you have any questions about this transmittal, please contact me at Mallory.Ress@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised plans
11/10/2020 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Completed
11/10/2020 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Completed
12/02/2020 JGARCIA1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
12/02/2020 JGARCIA1 APPROVAL SHELF Completed
12/02/2020 JGARCIA1 OUT TO CUSTOMER Completed
12/02/2020 JGARCIA1 REJECT SHELF Completed