Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T20CM06322
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/28/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 10/29/2020 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 10/29/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/30/2020 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | DP20-0147 must be approved first |
| 11/04/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | 11/04/20: Efficiency factor provided . [The efficiency factor called for in Section C403.10.2.1, IECC 2018 is the ratio of BTU of cooling produced per Watt-hour, not kWh per day. See Table C403.10.2.1 (3), IECC 2018.] [Second comment: Provide the system efficiency of the walk-in cooler and freezer. See Table C403.10.2.1 (3), IECC 2018.] [Initial comment: Show that the walk-in cooler/freezer meets the efficiency requirements of Section C403.10.2.1, IECC 2018.] |