Permit Number - T20CM06315
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/23/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Passed | |
| 10/23/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 10/23/2020 | DTRAMME1 | ENGINEERING | REVIEW | Passed | |
| 10/23/2020 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 10/26/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide a site plan showing the location of the power source and wiring methods for the electrical feeder to the transformer cart. 2. Provide a designated circuit and panel schedule complete with load calculations to verify sufficient capacity for the tent load. 3. If the tent is fully enclosed, please disregard comment #'s 4 and 5. 4. Provide plans and evidence on the plans that the proposed exterior lighting fully complies with the Outdoor Lighting Code. See section 104 for plan submittal requirements. 5. Provide lighting plans with the following information on the plans; (a) Provide a complete luminaire schedule. (b) Size of the parcel in acres. (c) See table 401.1, lighting area and option and indicate this information in the lighting site plan, also showing the locations and types of all exterior luminaires including existing. (d) 402.1 (light source color temperature requirements), shielding requirements, etc . (e) Provide calcs for total lumens allowed and total lumens proposed per acre including existing, for Full Cut Off and Unshielded per table 401.1. (f) Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2. (g) Specify any exceptions used. (h) Curfew lighting controls If applicable. Do not confuse the Outdoor Lighting Code with the IECC. You can appeal to the Chief Building Official for a temporary exemption to the requirements of the Outdoor Lighting Code per section 103.2. Application form can be submitted online from www.tucsonaz.gov/pdsd. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. 2012 Tucson/Pima County Outdoor Lighting Code |
| 10/26/2020 | ALEXANDRA HINES | ZONING | REVIEW | Approved | |
| 10/26/2020 | AHINES2 | OIP | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/28/2020 | IMONSHI1 | OUT TO CUSTOMER | Completed |