Permit Number: T20CM06305
Parcel: 132101810

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T20CM06305
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/15/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Show gas pipe sizes in compliance with connected demand, G2413.3 & Table G2413.4(1). A 3/4" pipe is limited to 170,000 BTU for a 37' total developed length sysem. Update the size to 1".

Final Status

Task End Date Reviewer's Name Type of Review Description
10/02/2020 VLEON1 APPROVAL SHELF Completed
10/02/2020 VLEON1 OUT TO CUSTOMER Completed
10/02/2020 VLEON1 REJECT SHELF Completed