Review Details: COMMERCIAL - TI

Permit Number - T20CM06287
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/16/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Passed
10/07/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Replacement of AC units constitutes new work so the submittal will require a heating/cooling load calculation to justify the capacities of the units being installed (Sections C403.3.1 and C403.2.2, IECC 2018). The units themselves will also have to comply with Sections C403.3.2, C403.4 and C403.5, IECC 2018 for efficiency, controls, and economizers. While ventilation calculations are not required, a test and balance report is required to verify that the total supply airflow and the outside airflow are at least equal to that which the previous AC unit provided.
10/12/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved